AWG to mm².
See the size behind the number.
Convert wire gauge to conductor area or diameter. The chart covers 4/0 through 40 AWG, with the units side by side.
Round conductor equivalent.
Insulation is not included. Drawing is not life size.
What is on your cable label?
0.08081 inches
Lower AWG numbers mean a thicker conductor. 1/0, 2/0, 3/0 and 4/0 continue the scale beyond 1 AWG.
3.309 square millimetres area, 2.053 millimetres diameter.
AWG to mm² and mm chart
Select a gauge to load it into the converter. Area and diameter describe the conductor, before insulation.
| AWG | Area mm² | Diameter mm | Diameter inches | Copper resistance Ω/km at 20 °C |
|---|---|---|---|---|
| 107.2 | 11.68 | 0.46 | 0.1608 | |
| 85.03 | 10.4 | 0.4096 | 0.2028 | |
| 67.43 | 9.266 | 0.3648 | 0.2557 | |
| 53.48 | 8.251 | 0.3249 | 0.3224 | |
| 42.41 | 7.348 | 0.2893 | 0.4066 | |
| 33.63 | 6.544 | 0.2576 | 0.5127 | |
| 26.67 | 5.827 | 0.2294 | 0.6464 | |
| 21.15 | 5.189 | 0.2043 | 0.8152 | |
| 16.77 | 4.621 | 0.1819 | 1.028 | |
| 13.3 | 4.115 | 0.162 | 1.296 | |
| 10.55 | 3.665 | 0.1443 | 1.634 | |
| 8.366 | 3.264 | 0.1285 | 2.061 | |
| 6.634 | 2.906 | 0.1144 | 2.599 | |
| 5.261 | 2.588 | 0.1019 | 3.277 | |
| 4.172 | 2.305 | 0.09074 | 4.132 | |
| 3.309 | 2.053 | 0.08081 | 5.211 | |
| 2.624 | 1.828 | 0.07196 | 6.571 | |
| 2.081 | 1.628 | 0.06408 | 8.285 | |
| 1.65 | 1.45 | 0.05707 | 10.45 | |
| 1.309 | 1.291 | 0.05082 | 13.17 | |
| 1.038 | 1.15 | 0.04526 | 16.61 | |
| 0.823 | 1.024 | 0.0403 | 20.95 | |
| 0.6527 | 0.9116 | 0.03589 | 26.41 | |
| 0.5176 | 0.8118 | 0.03196 | 33.31 | |
| 0.4105 | 0.7229 | 0.02846 | 42 | |
| 0.3255 | 0.6438 | 0.02535 | 52.96 | |
| 0.2582 | 0.5733 | 0.02257 | 66.78 | |
| 0.2047 | 0.5106 | 0.0201 | 84.21 | |
| 0.1624 | 0.4547 | 0.0179 | 106.2 | |
| 0.1288 | 0.4049 | 0.01594 | 133.9 | |
| 0.1021 | 0.3606 | 0.0142 | 168.9 | |
| 0.08098 | 0.3211 | 0.01264 | 212.9 | |
| 0.06422 | 0.2859 | 0.01126 | 268.5 | |
| 0.05093 | 0.2546 | 0.01003 | 338.5 | |
| 0.04039 | 0.2268 | 0.008928 | 426.9 | |
| 0.03203 | 0.2019 | 0.00795 | 538.3 | |
| 0.0254 | 0.1798 | 0.00708 | 678.8 | |
| 0.02014 | 0.1601 | 0.006305 | 856 | |
| 0.01597 | 0.1426 | 0.005615 | 1,079 | |
| 0.01267 | 0.127 | 0.005 | 1,361 | |
| 0.01005 | 0.1131 | 0.004453 | 1,716 | |
| 0.007967 | 0.1007 | 0.003965 | 2,164 | |
| 0.006318 | 0.08969 | 0.003531 | 2,729 | |
| 0.00501 | 0.07987 | 0.003145 | 3,441 |
44 of 44 sizes shown. Values are calculated from the AWG progression and rounded for display. Cable manufacturers may publish slightly different nominal values or resistance limits.
AWG, mm and mm² measure different things
AWG is a gauge number. Millimetres measure diameter, while square millimetres measure cross-sectional area. For a round conductor, area is π × diameter² ÷ 4. Doubling diameter gives four times the area.
Area (mm²) = π × diameter² ÷ 4
For the formula: 1/0 = 0, 2/0 = −1, 3/0 = −2, 4/0 = −3
12 AWG is about 2.053 mm in diameter and 3.309 mm² in area. A 3.5 mm² conductor is closest to 12 AWG by area, but 12 AWG has only about 3.309 mm². If you need at least 3.5 mm², the next listed size is 11 AWG at about 4.172 mm². Check availability and the cable specifications before substituting sizes.
Reference and calculation method
The AWG progression and annealed-copper resistance reference come from NBS Handbook 100, Copper Wire Tables. We calculate geometry from the progression instead of rounding intermediate diameters. For a manufacturer reference, see Victron’s AWG to metric chart.
Reading a real cable label
Can I measure the outside of an insulated wire?
The outside measurement includes insulation, so it cannot directly tell you conductor area. Use the manufacturer’s conductor specification. The diameter here is for a solid round conductor with the stated area.
Does the chart work for stranded cable?
Its area describes the total conducting metal. A stranded bundle has gaps and a different outside diameter, so this solid-round equivalent is not a measurement of the finished bundle. Use the cable datasheet for physical fit and maximum resistance.
Is 10 AWG the same as 6 mm²?
10 AWG is about 5.261 mm². A 6 mm² conductor has more area. They may appear near each other in reference tables, but they are not exact equivalents. Check electrical and mechanical requirements before substituting one for the other.
Does the gauge tell me the maximum current?
Gauge describes conductor size. Current capacity also depends on the material, insulation, temperature, bundling and installation. This chart does not assign a universal amp rating to a gauge. Use the wire-sizing tool to check voltage drop, then verify ampacity separately.